Analog input (ADC)

Number: 1
Parameter range:

P0750 – P0762

Function chart number:

FP2200

Features:

- cycle time:

4 ms

- resolution:

10 bits

- accuracy:

1 % referred to 10 V / 20 mA

- electrical features:

incorrect polarity protection, short-circuit proof

Analog setpoints, actual values and control signals are read-into the drive inverter
using the appropriate analog input and are converted into digital signals / values
using the ADC converter.
The analog input represents a voltage input that can be additionally configured via
parameter P0756.

Depending on the source, the appropriate connection must be made. Using, as an
example, the internal 10 V voltage source, a connection is shown as an example in
the following diagram (refer to Fig. 3-24).

Voltage input

A

D

KL1 10 V

KL2 0 V

KL4 ADC

KL3 ADC+

> 4.7 k

Fig. 3-24

Connection example for ADC voltage input

The ADC channel has several function units (filter, scaling, dead zone) (refer to
Fig. 3-25).

KL

KL

A

D

ADC

type

ADC

scaling

P

0757

P

0758

P

0759

P

0760

ADC

dead

zone

r0755

Pxxxx

r0752

P1000

ADC

ADC+

r0754

P0761

P0753

P0756

Setpoint

ADC channel

r0722
r0722.3

0

1

1.7 V

3.9 V

Wire

breakage

sensing

P0756 P0761

r0751

F0080

P0704

Pxxxx

Function

Fig. 3-25

ADC channel