beautypg.com

9 motorized potentiometer (mop) – Siemens MICROMASTER 420 User Manual

Page 102

background image

3 Functions

Issue 07/04

MICROMASTER 420 Operating Instructions

102

6SE6400-5AA00-0BP0

3.9

Motorized potentiometer (MOP)

Parameter range:

P1031 – r1050

Warnings -
Faults -

Function chart number:

FP3100

This function emulates an electromechanical potentiometer to enter setpoints. The
motorized potentiometer value is adjusted using the "Raise" and "Lower control
signal" which is selected using BICO parameters P1035 and P1036 (refer to Fig.
3-34). The value which has been set is available through connector output r1050
so that it can be further connected and used.

P1120

f

P1080

"1"
"0"

"1"
"0"

t

t

t

DIN

BOP

USS

BOP link

USS

COM link

CB

COM link

"1"
"0"

t

P1082

P1121

P1035

P1036

P0840

-P1080

r1050

f

act

-P1082

Fig. 3-34

Motorized potentiometer

Selecting via serial interfaces

The MOP functionality can be selected via the operator panels (refer to Section
3.1.3), digital inputs as well as via serial interfaces (refer to the example).
Parameterization is also possible directly using BICO parameters P1035 and
P1036 as well as also parameters P0700 and P0719. In this case, for a value
assigned to P0700, the BICO parameter is appropriately modified.

Example:

Command source via "USS on BOP link" interface

a) Standard method

P0700 = 4

b) BICO method

P1035 = 2032.13

P1036 = 2032.14

::::

(refer to P0700 for a complete list)