3.21.1.5

Current limiting (Imax controller)

Parameter range:

P1340 – P1344

r0056 bit 13

Warnings A0501
Faults F0001
Function chart number:

FP6100

Our drive inverters have, in the V/f characteristic mode, a current limiting controller
(Imax controller, refer to Fig. 3-64). This controller avoids overload conditions. This
controller protects the drive inverter and the motor against continuous overload
conditions by automatically reducing the drive inverter output frequency by f

Imax

(r1343) or the drive inverter output voltage by V

Imax

(r1344). By either reducing the

output frequency or the output voltage, this reduces the load on the drive inverter
and protects against continuous damage.

Imax controller setpoint

+

r1343

CO:Imax ctrl Foutp

r1344

CO:Imax ctrl Voutp

Current feedback

r0067

CO: Outp cur limit [A]

r0068

CO: Output current [A]

Motor ovl fact [%]

10.0 ... 400.0 [%]

P0640.D (150.0)

Motor temperatur
Inverter temperatur
i

2

t inverter

Motor ovl fact [%]

10.0 ... 400.0 [%]

P0640.D (150.0)

Imax ctrl prp gain

0.000 ... 5.499

P1345.D (0.250)

Kp

Tn

Kp

Tn

Imax ctrl int time

0.000 ... 50.000 [s]

P1346.D (0.300)

Imax ctrl prp gain

0.000 ... 0.499

P1340.D (0.000)

Imax ctrl int time

0.000 ... 50.000 [s]

P1346.D (0.300)

U

I_max

f

I_max

Fig. 3-64

Imax controller

NOTE
A reduction in the frequency only reduces the load if the load decreases at lower
speeds (e.g. square-law torque-speed characteristic of the driven load).