beautypg.com

3 calculating the motor / control data – Siemens MICROMASTER 420 User Manual

Page 69

background image

Issue 07/04

3 Functions

MICROMASTER 420 Operating Instructions

6SE6400-5AA00-0BP0

69

3.5.3

Calculating the motor / control data

Internal motor / control data is calculated using parameter P0340 or, indirectly
using parameter P3900 (refer to Section 3.5.2) or P1910 (refer to Section 3.5.4).
The functionality of parameter P0340 can, for example, if the motor weight or the
stator resistance is known. The following settings are possible for P0340:
0 No

calculation

1 Complete

parameterization

For the complete parameterization (P0340 = 1), in addition to the motor / control
parameters, parameters are also pre-assigned which refer to the motor rated data
(e.g. torque limits and reference quantities for interface signals).

Table 3-9

Parameter for motor/control data

P0344 Motor weight

P2002 Reference current

P2000 Reference frequency

P0350 Stator resistance (line-to-line)
P0611 Motor I2t time constant

P0346 Magnetization time

P1253 Vdc-controller output limitation

P0347 Demagnetization time

P1316 Boost end frequency

x
x
x

x

x

x
x
x
x

P0340 = 1

NOTE

When exiting the quick commissioning with P3900 > 0 (refer to Section 3.5.2),
internally P0340 is set to 1 (complete parameterization).

For the motor data identification (refer to Section 3.5.4), after the measurement
has been completed, internally P0340 is set to 3.