3 calculating the motor / control data – Siemens MICROMASTER 420 User Manual
Page 69
Issue 07/04
3 Functions
MICROMASTER 420 Operating Instructions
6SE6400-5AA00-0BP0
69
3.5.3
Calculating the motor / control data
Internal motor / control data is calculated using parameter P0340 or, indirectly
using parameter P3900 (refer to Section 3.5.2) or P1910 (refer to Section 3.5.4).
The functionality of parameter P0340 can, for example, if the motor weight or the
stator resistance is known. The following settings are possible for P0340:
0 No
calculation
1 Complete
parameterization
For the complete parameterization (P0340 = 1), in addition to the motor / control
parameters, parameters are also pre-assigned which refer to the motor rated data
(e.g. torque limits and reference quantities for interface signals).
Table 3-9
Parameter for motor/control data
P0344 Motor weight
P2002 Reference current
P2000 Reference frequency
P0350 Stator resistance (line-to-line)
P0611 Motor I2t time constant
P0346 Magnetization time
P1253 Vdc-controller output limitation
P0347 Demagnetization time
P1316 Boost end frequency
x
x
x
x
x
x
x
x
x
P0340 = 1
NOTE
When exiting the quick commissioning with P3900 > 0 (refer to Section 3.5.2),
internally P0340 is set to 1 (complete parameterization).
For the motor data identification (refer to Section 3.5.4), after the measurement
has been completed, internally P0340 is set to 3.