beautypg.com

Siemens MICROMASTER 420 User Manual

Page 83

background image

Issue 07/04

3 Functions

MICROMASTER 420 Operating Instructions

6SE6400-5AA00-0BP0

83

P2267 =...

Max. value for PID feedback
Sets the upper limit for the value of the feedback signal in [%]

P2268 =...

Min. value for PID feedback
Sets lower limit for value of feedback signal in [%]

P2280 =...

PID proportional gain
Allows user to set proportional gain for PID controller

P2285 =...

PID integral time
Sets integral time constant for PID controller

P2291 =...

PID output upper limit
Sets upper limit for PID controller output in [%]

P2292 =...

PID output lower limit
Sets lower limit for the PID controller output in [%]

PID

MOP

ADC

PID

SUM

PID

PID

FF

USS

BOP link

USS

COM link

CB

COM link

P2254

P2253

PID

RFG

PID

PT1

− ∆

PID

P2200

P2264

PID

PT1

PID

SCL

Output

PID

0

1

Motor

control

P

2257

P

2258

P

2261

P2271

P

2269

P

2270

P2265

P2280

P2285

P2268

P2267

P2292

P2291

r2273

r2294

Example:

Parameter Parameter

text

Example

P2200

BI: Enable PID controller

P2200 = 1.0

PID controller active

P2253

CI: PID setpoint

P2253 = 2224 PID-FF1

P2264

CI: PID feedback

P2264 = 755 ADC

P2267

Max. PID feedback

P2267

Adapt to the application

P2268

Min. PID feedback

P2268

Adapt to the application

P2280

PID proportional gain

P2280

Determined by optimizing

P2285

PID integral time

P2285

Determined by optimizing

P2291

PID output upper limit

P2291

Adapt to the application

P2292

PID output lower limit

P2292

Adapt to the application


NOTE
If P0971 is used to start data save from the RAM to EEPROM, then after the data
has been transferred, the communications memory is re-initialized. This means that
communications via USS as well as also via the CB board are interrupted for the
time it takes to reset:

The connected PLC (e.g. SIMATIC S7) goes into stop

The STARTER start-up program buffers the communications failure

For the DriveMonitor start-up program, "NC" (not connected) or "drive busy" is
displayed.

The "busy" text is displayed at the BOP operator panel

After reset has been completed, for the start-up programs STARTER and
DriveMonitor and the BOP operator panel, communications are automatically re-
established.

100.00 %

0.00 %

3.000

0.000 s

100.00 %

0.00 %