beautypg.com

10 jog, 11 ramp-function generator (hlg) – Siemens MICROMASTER 420 User Manual

Page 77

background image

Issue 07/04

3 Functions

MICROMASTER 420 Operating Instructions

6SE6400-5AA00-0BP0

77

P1016 =... Fixed frequency code –

Bit 0

Defines the selection method for fixed
frequencies.

P1017 =... Fixed frequency code –

Bit 1

P1018 =... Fixed frequency code –

Bit 2

1 Direct selection
2 Direct selection + ON command
3 Binary coded selection + ON command
NOTE
For settings 2 and 3, all parameters P1016 to
P1019 must be set to the selected value so that
the drive inverter accepts the ON command.

3.5.5.10 JOG

P1058 =...

JOG frequency right
Frequency in Hz when the motor is being
jogged in the clockwise direction of rotation.

P1059 =...

JOG frequency left
Frequency in Hz when the motor is being
jogged in the counter-clockwise direction of
rotation.

P1060 =...

JOG ramp-up time
Ramp-up time in s from 0 to the maximum
frequency (P1082). The JOG ramp-up is
limited by P1058 or P1059.

P1061 =...

JOG ramp-down time
Ramp-down time in s from the maximum
frequency (P1082) to 0.

P1082
(f

max

)

P1058

t

P1060

P1061

f

JOG

3.5.5.11

Ramp-function generator (HLG)

P1091 =...

Skip frequency 1

(entered in Hz)

Defines skip frequency 1 which avoids
effects of mechanical resonance and
suppresses frequencies within +/- P1101
(skip frequency bandwidth).

P1091 =...

Skip frequency 2

P1091 =...

Skip frequency 3

P1091 =...

Skip frequency 4

P1101 =...

Skip frequency bandwidth
(entered in Hz)

P1101

P1091

f

in

f

out

Skip frequency

bandwidth

Skip frequency

P1120 =...

Ramp-up time
(enters the accelerating time in s)

P1121 =...

Ramp-down time
(enters the deceleration time in s)

f

P1082
(f

max

)

f

1

t

P1120

P1121

1

1

1

10.00 s

10.00 s

5.00 Hz

5.00 Hz

2.00 Hz

0.00 Hz

0.00 Hz

0.00 Hz

0.00 Hz

10.00 s

10.00 s