beautypg.com

2 pid fixed setpoint (pid-ff) – Siemens MICROMASTER 420 User Manual

Page 109

background image

Issue 07/04

3 Functions

MICROMASTER 420 Operating Instructions

6SE6400-5AA00-0BP0

109

3.11.2

PID fixed setpoint (PID-FF)

Number: 7
Parameter range:

P2201 – r2224

Warnings -
Faults -
Function chart number:

FP3300, FP3310

Analog to the fixed frequencies (refer to Section 3.8), the PID controller has
separate programmable PID fixed setpoints. The values are defined using
parameters P2201 – P2207 and are selected using binector inputs P2220 – P2222.
The selected PID fixed setpoint is available via connector output r2224 where it can
be further processed (e.g. as PID main setpoint

P2253 = 2224).

3 methods are available to select the PID fixed setpoints, analog to the fixed
frequencies (Section 3.8):

Direct selection

Direct selection + ON command

Binary-coded selection + ON command

The methods are selected using parameters P2216 – P2218.

P2216

P0701 = 15
or
P0701 = 99, P2220 = 722.0, P2216 = 1

DIN1

r2224

r0722.0

P2220

1

2,3

P2201

0

. . . .

0

. . .

.

. . . .

Fig. 3-38

Example to directly select the PID fixed frequency of fixed frequency 1 via
DIN1