3 Functions
Issue 07/04
MICROMASTER 420 Operating Instructions
114
6SE6400-5AA00-0BP0
Table 3-19
BICO parameters for ramp-function generator
Parameter Description
P1140
BI: RFG enable
The ramp-function generator output is set to 0 if the
binary signal = 0.
P1141
BI: RFG start
The ramp-function generator output keeps its actual
value if the binary signal = 0.
P1142
BI: RFG enable setpoint
If the binary signal = 0, then the ramp-function
generator input is set to 0 and the output is reduced
to 0 via the ramp-function generator ramp.
The ramp-function generator itself is enabled after the pulses have been enabled
(inverter enable) and after the excitation time has expired (P0346). After limiting to
the maximum speeds for the positive and negative directions of rotation (P1082,
-P1082 or 0 Hz for the direction of rotation inhibit) the setpoint speed for the control
is obtained (r1170).
NOTE
The maximum drive inverter frequency is defined in the setpoint channel using
parameter P1080. The maximum possible frequency is 650 Hz.