Issue 07/04

3 Functions

MICROMASTER 420 Operating Instructions

6SE6400-5AA00-0BP0

115

3.12.3 OFF/braking

functions

Parameter range:

P1121, P1135, P2167, P2168

P0840 – P0849

r0052 bit 02

Warnings -
Faults -

Function chart number:

-

The drive inverter and the user must respond to an extremely wide range of
situations and stop the drive. In this case, both requirements relating to operations
as well as drive inverter protective functions (e.g. electrical and thermal overload)
and man-machine protective functions have to be taken into account. As a result of
the different OFF/braking functions (OFF1, OFF2, OFF3) MICROMASTER can
flexibly respond to the requirements mentioned above.

OFF1

The OFF1 command is closely coupled to the ON command. When the ON
command is withdrawn, then OFF1 is directly activated. The drive is braked by
OFF1 with the ramp-down time P1121. If the output frequency falls below the
parameter value P2167 and if the time in P2168 has expired, then the inverter
pulses are cancelled.

t

P2168

t

P2167

Operation

act

f

OFF1

P1082

f

max

r0052 Bit02

P1121

P1082

f

P1121

t

2

1

OFF

,

down

=

t

down,OFF1

Pulse

cancellation

Fig. 3-44

OFF1

NOTE

OFF1 can be entered using a wide range of command sources via BICO
parameter P0840 (BI: ON/OFF1) and P0842 (BI: ON/OFF1 with reversing).

BICO parameter P0840 is pre-assigned by defining the command source using
P0700.

The ON and the following OFF1 command must have the same source.

If the ON/OFF1 command is set for more than one digital input, then only the
digital input that was last set, is valid, e.g. DIN3 is active.

OFF1 can be combined with DC current braking or compound braking.

When the motor holding brake MHB (P1215) is activated, for an OFF1, P2167
and P2168 are not taken into account.