2 digital output (dout) – Siemens MICROMASTER 420 User Manual

Page 90

background image

3 Functions

Issue 07/04

MICROMASTER 420 Operating Instructions

90

6SE6400-5AA00-0BP0

3.6.2

Digital output (DOUT)

Number: 1
Parameter range:

r0730 – P0748

Function chart number:

FP2100

Features:

- cycle time:

1 ms

Binary states in the drive can be output via the digital output. As result of the fast
cycle time, it is possible to control external devices and to display the state in real
time. In order that higher powers can also be output, the internal signal (TTL level)
is amplified using a relay (refer to Fig. 3-23).

Relay:

- max. opening / closing time:

5 / 10 ms

- voltage / current

30 V DC / 5 A

250 V AC / 2 A

(52:7)

BI: Fct. of DOUT 2

P0732.C

-1

0

2

Invert DOUTs

0 ... 7

P0748 (0)

CO/BO: State DOUTs

r0747

r0747

NO

COM

Kl.11

Kl.10

.1

Fig. 3-23

Digital output

The states, which are to be output, are defined using the "BI" parameter P0731
(digital output). For the definition, the "BO" parameter number or "CO/BO"
parameter number and the bit number of the particular state should be entered into
P0731. Frequently used states including the parameter number and bit are shown
in the following Table (refer to Table 3-11).