beautypg.com

6 inputs / outputs, 1 digital inputs (din) – Siemens MICROMASTER 420 User Manual

Page 87

background image

Issue 07/04

3 Functions

MICROMASTER 420 Operating Instructions

6SE6400-5AA00-0BP0

87

3.6

Inputs / outputs

3.6.1

Digital inputs (DIN)

Number:

3 + 1

Parameter range:

r0722 – P0725

Function chart number:

FP2000, FP2200

Features:

- cycle time:

2 ms

- switch-on threshold:

10.6 V

- switch-out threshold: 10.6 V
- electrical features:

electrically isolated, short-circuit proof

External control signals are required for a drive converter to be able to operate
autonomously. These signals can be entered via a serial interface as well as also
via digital inputs (refer to Fig. 3-22). MICROMASTER has 3 digital inputs which can
be expanded to a total of 4 by using the 2 analog inputs. The digital inputs, as far
as their assignment, can be freely programmed to create a function. Whereby,
regarding the program, it is possible to directly assign the function via parameters
P0701 - P0704 or to freely program the function using BICO technology.

DIN channel (e.g. DIN1 - PNP (P0725 = 1))

24 V

T

0

&

0

1

PNP/NPN DIN

0 ... 1

P0725 (1)

0 V

24 V

Debounce time: DIN

0 ... 3

P0724 (3)

CO/BO: Bin.inp.val

r0722

r0722

.0

Kl.8
P24 (PNP)
Kl.9
0 V (NPN)

Pxxxx BI: ...

P0701

Function

0

1

DIN channel (e.g. DIN1 - NPN (P0725 = 0))

24 V

T

0

&

0

1

PNP/NPN DIN

0 ... 1

P0725 (1)

0 V

24 V

Debounce time: DIN

0 ... 3

P0724 (3)

CO/BO: Bin.inp.val

r0722

r0722

.0

Kl.8
P24 (PNP)
Kl.9
0 V (NPN)

Pxxxx BI: ...

P0701

Function

0

1

Fig. 3-22

Digital inputs