beautypg.com

Siemens MICROMASTER 420 User Manual

Page 160

background image

5 MICROMASTER 420 specifications

Issue 07/04

MICROMASTER 420 Operating Instructions

160

6SE6400-5AA00-0BP0

Table 5-4

MICROMASTER 420 Specifications

In order to have a UL compliant installation fuses from the SITOR range with the
appropriate current rating must be used.

Input voltage range

1 AC 200 V – 240 V, ± 10 %

(with built in Class A Filter)

Order No.

6SE6420- 2AB11

-2AA1

2AB12

-5AA1

2AB13

-7AA1

2AB15

-5AA1

2AB17

-5AA1

2AB21

-1BA1

2AB21

-5BA1

2AB22

-2BA1

2AB23

-0CA1

[kW] 0.12 0.25 0.37 0.55

0.75 1.1 1.5 2.2 3.0

Output Rating

[hp] 0.16

0.33 0.5 0.75 1.0 1.5 2.0 3.0 4.0

Output

Power

[kVA] 0.4 0.7 1.0 1.3 1.7 2.4 3.2 4.6 6.0

Input Current 1)

[A]

1.8

3.2

4.6

6.2

8.2

11.0

14.4

20.2

35.5

Output

Current

[A] 0.9 1.7 2.3 3.0 3.9 5.5 7.4 10.4 13.6

Fuse

[A] 10 10 10 10 16 20 20 32 40

Recommended

3NA 3803 3803 3803 3803 3805 3807 3807 3812 3817

For UL specified

* * * * * * * * *

[mm

2

] 1.0 1.0 1.0 1.0 1.0 2.5 2.5 4.0 6.0

Input Cable, min.

[awg] 17 17 17 17 17 15 15 11 9

[mm

2

] 2.5 2.5 2.5 2.5 2.5 6.0 6.0 6.0 10.0

Input Cable, max.

[awg] 13 13 13 13 13 9 9 9 7

[mm

2

] 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.5

Output Cable, min.

[awg] 17 17 17 17 17 17 17 17 15

[mm

2

] 2.5 2.5 2.5 2.5 2.5 6.0 6.0 6.0 10.0

Output Cable, max.

[awg] 13 13 13 13 13 9 9 9 7

[kg] 1.2 1.2 1.2 1.3 1.3 3.3 3.6 3.6 5.2

Weight

[lbs]

2.6 2.6 2.6 2.9 2.9 7.3 7.9 7.9 11.4

1) Secondary conditions: Input current at the rated operating point - applies for the short-circuit voltage of the line

supply V

k

= 1 % referred to the rated drive converter power and a rated line supply voltage

of 240 V without line commutating reactor. If a line commutating reactor is used, the
specified values are reduced by between 55 % and 70 %.

* UL listed fuses such as Class NON from Bussmann are required for use in America