5 MICROMASTER 420 specifications
Issue 07/04
MICROMASTER 420 Operating Instructions
160
6SE6400-5AA00-0BP0
Table 5-4
MICROMASTER 420 Specifications
In order to have a UL compliant installation fuses from the SITOR range with the
appropriate current rating must be used.
Input voltage range
1 AC 200 V – 240 V, ± 10 %
(with built in Class A Filter)
Order No.
6SE6420- 2AB11
-2AA1
2AB12
-5AA1
2AB13
-7AA1
2AB15
-5AA1
2AB17
-5AA1
2AB21
-1BA1
2AB21
-5BA1
2AB22
-2BA1
2AB23
-0CA1
[kW] 0.12 0.25 0.37 0.55
0.75 1.1 1.5 2.2 3.0
Output Rating
[hp] 0.16
0.33 0.5 0.75 1.0 1.5 2.0 3.0 4.0
Output
Power
[kVA] 0.4 0.7 1.0 1.3 1.7 2.4 3.2 4.6 6.0
Input Current 1)
[A]
1.8
3.2
4.6
6.2
8.2
11.0
14.4
20.2
35.5
Output
Current
[A] 0.9 1.7 2.3 3.0 3.9 5.5 7.4 10.4 13.6
Fuse
[A] 10 10 10 10 16 20 20 32 40
Recommended
3NA 3803 3803 3803 3803 3805 3807 3807 3812 3817
For UL specified
* * * * * * * * *
[mm
2
] 1.0 1.0 1.0 1.0 1.0 2.5 2.5 4.0 6.0
Input Cable, min.
[awg] 17 17 17 17 17 15 15 11 9
[mm
2
] 2.5 2.5 2.5 2.5 2.5 6.0 6.0 6.0 10.0
Input Cable, max.
[awg] 13 13 13 13 13 9 9 9 7
[mm
2
] 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.5
Output Cable, min.
[awg] 17 17 17 17 17 17 17 17 15
[mm
2
] 2.5 2.5 2.5 2.5 2.5 6.0 6.0 6.0 10.0
Output Cable, max.
[awg] 13 13 13 13 13 9 9 9 7
[kg] 1.2 1.2 1.2 1.3 1.3 3.3 3.6 3.6 5.2
Weight
[lbs]
2.6 2.6 2.6 2.9 2.9 7.3 7.9 7.9 11.4
1) Secondary conditions: Input current at the rated operating point - applies for the short-circuit voltage of the line
supply V
k
= 1 % referred to the rated drive converter power and a rated line supply voltage
of 240 V without line commutating reactor. If a line commutating reactor is used, the
specified values are reduced by between 55 % and 70 %.
* UL listed fuses such as Class NON from Bussmann are required for use in America