3 Functions

MICROMASTER 420 Operating Instructions

6SE6400-5AA00-0BP0

49

In order to interconnect two signals, a BICO setting parameter (signal receiver)
must be assigned the required BICO monitoring parameter (signal source). A
typical BICO interconnection is shown using the following examples (refer to Fig.
3-6).

Connector output (CO) ===> Connector input (CI)

CO/BO: Act. status word 1

FB

r0755

P1070 = 755

(755)

P1070

FB

P0840 = 751.0

r0751

(751:0)

P0840

FB

(751:0)

P0840

(751:0)

P0840

P0731 = 52.3

P2051 = 52

P0731

FB

P0731

(52:3)

P0731

FB

P2051

(52)

FB

r0052

r0052

Binector output (BO) ===> Binector input (BI)

Connector output / Binector output (CO/BO)

BO: Status word of ADC

CO: Act. ADC after scal. [4000h]

CI: Main setpoint

BI: ON/OFF1

CI: PZD to CB

BI: Function of digital output 1

Function

Function

Function

Function

Function

Function

Function

Fig. 3-6

BICO connections (examples)

NOTE
BICO parameters with the CO, BO or CO/BO attributes can be used a multiple
number of times.