beautypg.com

3 mechanical installation – Siemens MICROMASTER 420 User Manual

Page 25

background image

Issue 07/04

2 Installation

MICROMASTER 420 Operating Instructions

6SE6400-5AA00-0BP0

25

2.3 Mechanical

installation

WARNING

To ensure the safe operation of the equipment, it must be installed and
commissioned by qualified personnel in full compliance with the warnings laid
down in these operating instructions.

Take particular note of the general and regional installation and safety
regulations regarding work on dangerous voltage installations (e.g. EN
50178), as well as the relevant regulations regarding the correct use of tools
and personal protective gear.

The mains input, DC and motor terminals, can carry dangerous voltages even
if the inverter is inoperative; wait 5 minutes to allow the unit to discharge after
switching off before carrying out any installation work.

The inverters can be mounted adjacent to each other. If they are mounted on
top of each other, however, a clearance of 100 mm has to be observed.

4

160 mm

6.30"

55 mm

2.2"

Ø 4.5 mm

0.17"

Ø 4.8 mm

0.19"

174 mm

6.85"

138 mm

5.43"

Ø 5.5 mm

0.22"

204 mm

8.03"

174 mm

6.85"

Frame Size A

Frame Size B

Frame Size C

Fig. 2-4

Drill pattern for MICROMASTER 420

Table 2-1

Dimensions and Torques of MICROMASTER 420

Frame-Size

Overall Dimensions

Fixing Method

Tightening Torque

mm

73 x 173 x 149

A

Width x
Height x
Depth

inch

2.87 x 6.81 x 5.87

2 x M4 Bolts
2 x M4 Nuts
2 x M4 Washers for mounting on
standard

rail

2.5 Nm
with washers fitted

mm

149 x 202 x 172

B

Width x
Height x
Depth

inch

5.87 x 7.95 x 6.77

4 x M4 Bolts
4 x M4 Nuts
4 x M4 Washers

2.5 Nm
with washers fitted

mm

185 x 245 x 195

C

Width x
Height x
Depth

inch

7.28 x 9.65 x 7.68

4 x M5 Bolts
4 x M5 Nuts
4 x M5 Washers

2.5 Nm
with washers fitted