3 Functions

MICROMASTER 420 Operating Instructions

6SE6400-5AA00-0BP0

113

In order to avoid torque surges at the transitions (constant velocity phase

←→

accelerating / braking phase), additional rounding-off times P1130 – P1133 can be
programmed. This is especially important for applications (e.g.
transporting/pumping liquids or for cranes) which require an especially "soft", jerk-
free acceleration and braking.

If the OFF1 command is initiated while the drive is accelerating, then rounding-off
can be activated or de-activated using parameter P1134 (refer to Fig. 3-43). These
rounding-off times are defined using parameters P1132 and P1133.

f

OFF1

ON

t

Setpoint reached

f

Set

t

f

P1132 > 0
P1133 > 0

P1132

Setpoint reached

Setpoint not reached

f

Set

t

Setpoint not reached

P1134 = 0

P1134 = 1

P1133

P1133

P1132

P1132

P1133

P1133

Fig. 3-43

Rounding off after an OFF1 command

In addition to the rounding-off times, the ramp-function generator can be influenced
using external signals. The ramp-function generator provides the following
functionality using BICO parameters P1140, P1141 and P1142.