5 MICROMASTER 420 specifications
MICROMASTER 420 Operating Instructions
6SE6400-5AA00-0BP0
161
Input voltage range
1 AC 200 V – 240 V, ± 10 %
(Unfiltered)
Order No.
6SE6420- 2UC11
-2AA1
2UC12
-5AA1
2UC13
-7AA1
2UC15
-5AA1
2UC17
-5AA1
2UC21
-1BA1
2UC21
-5BA1
2UC22
-2BA1
2UC23
-0CA1
[kW]
0.12 0.25 0.37 0.55
0.75 1.1 1.5 2.2 3.0
Output Rating
[hp]
0.16 0.33 0.5
0.75 1.0 1.5 2.0 3.0 4.0
Output Power
[kVA]
0.4 0.7 1.0 1.3 1.7 2.4 3.2 4.6 6.0
Input
Current
1)
[A] 1.8 3.2 4.6 6.2 8.2 11.0 14.4 20.2 35.5
Output
Current
[A] 0.9 1.7 2.3 3.0 3.9 5.5 7.4 10.4 13.6
Fuse
[A] 10 10 10 10 16 20 20 32 40
Recommended
3NA 3803 3803 3803 3803 3805 3807 3807 3812 3817
For UL specified
* * * * * * * * *
[mm
2
]
1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 2.5
Input Cable, min.
[awg]
17 17 17 17 17 17 17 17 13
[mm
2
]
2.5 2.5 2.5 2.5 2.5 6.0 6.0 6.0
10.0
Input Cable, max.
[awg]
13 13 13 13 13 9 9 9 7
[mm
2
]
1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.5
Output Cable, min.
[awg]
17 17 17 17 17 17 17 17 15
[mm
2
]
2.5 2.5 2.5 2.5 2.5 6.0 6.0 6.0
10.0
Output Cable, max.
[awg]
13 13 13 13 13 9 9 9 7
[kg]
1.2 1.2 1.2 1.2 1.2 2.9 2.9 3.1 5.2
Weight
[lbs]
2.6 2.6 2.6 2.6 2.6 6.4 6.4 6.8
11.4
Input voltage range
3 AC 200 V – 240 V, ± 10 %
(with built in Class A Filter)
Order No.
6SE6420- 2AC23
-0CA1
2AC24
-0CA1
2AC25
-5CA1
[kW]
3.0 4.0 5.5
Output Rating
[hp]
4.0 5.0 7.5
Output Power
[kVA]
6.0 7.7 9.6
Input Current 1)
[A]
15.6 19.7 26.3
Output Current
[A]
13.6
17.5
22.0
Fuse [A]
25 32 35
Recommended
3NA
3810
3812
3814
For UL specified
* * *
[mm
2
]
2.5 2.5 4.0
Input Cable, min.
[awg]
13 13 11
[mm
2
]
10.0 10.0 10.0
Input Cable, max.
[awg]
7 7 7
[mm
2
]
1.5 2.5 4.0
Output Cable, min.
[awg]
15 13 11
[mm
2
]
10.0 10.0 10.0
Output Cable, max.
[awg]
7 7 7
[kg]
5.2 5.5 5.5
Weight
[lbs]
11.4 12.1 12.1
1) Secondary conditions: Input current at the rated operating point - applies for the short-circuit voltage of the line
supply V
k
= 1 % referred to the rated drive converter power and a rated line supply voltage
of 240 V without line commutating reactor. If a line commutating reactor is used, the
specified values are reduced by between 55 % and 70 %.
* UL listed fuses such as Class NON from Bussmann are required for use in America