Parameter Setup

Parameters for Full-Closed Control

7B

*

(F)

1 to 10000

<100>

16 x

external

scale

pulse

Hybrid deviation

error level

• You can setup the permissible gap (hybrid deviation) between the

present motor position and the present external scale position.

7C

*

(F)

0 to 1

<0>

External scale

direction

You can set up the logic of the absolute data of the external scale.


Unlike 16.Pr50 (setup of operating direction), this parameter depends on
the mounting direction of external scale. Please note that the full-closed
control cannot be executed appropriately in a reverse setting.

78

*

(F)

79

*

(F)

7A

*

(F)

0 to 32767

<10000>

0 to 17

<0>

1 to 32767

<10000>

Numerator of

external scale

ratio

Multiplier of

numerator of

external scale

ratio

Denominator of

external scale

ratio

You can setup the ratio between the encoder resolution and the external
scale resolution at full-closed control.

• SV.Pr78= 0
Numerator equals to encoder resolution, and you can setup
the external scale resolution per one motor revolution with SV.Pr7A.
• SV.Pr78

0,

Setup the ratio between the external scale resolution and the encoder

resolution per one motor revolution according to the above formula.


• Upper limit of numerator value after calculation is 131072. Setup

exceeding this value will be invalidated, and 131702 will be the actual
numerator.

• The actual calculation of numerator is “numerator of external scale

division (SV.Pr78) x 2 to the nth power (a set value of SV.Pr79)”.

Encoder resolution per one motor revolution

External scale resolution per one motor revolution

SV.Pr78 X 2

SV.Pr79

SV.Pr7A

=

Setup value

0

1

Content

Serial data will increase when the detection head travels

to the right viewed from the mounting side. (+ count)

Serial data will decrease when the detection head travels

to the right viewed from the mounting side. (– count)

Standard default : < >

Servo

PrNo.

Setup

range

Unit

Title

Function/Content

Standard default : < >

Servo

PrNo.

Setup

range

Unit

Title

Function/Content

73

0 to 20000

<0>

r/min

Setup of

over-speed level

• You can set up the over-speed level. The over-speed level becomes 1.2

times of the motor max. speed by setting up this to 0.

• Use this with 0 setup in normal operation. Set up other value only when

you need to lower the over-speed level.

• The setup value of this parameter is limited by 1.2 times of the motor

max. speed.


The detection error against the setup value is

±

3 [r/min] in case of the 7-wire

absolute encoder, and

±

36 [r/min] in case of the 5-wire incremental encoder.


• Anything marked with “(F)” on the servo parameter number (Servo PrNo.) can be used only for the “Full-

Closed Control”.

• For servo parameters which No. have a suffix of "*", changed contents will be validated when you turn on

the control power.