beautypg.com

Setting – Panasonic MINAS A4P Series User Manual

Page 69

background image

69

[Setting]

Setting

Standard default : < >

Servo

PrNo.

Setup

range

Unit

Title

Function/Content

65

0 to 1

<1>

Undervoltage error

response at main

power-off

You can select whether or not to activate Err13 (Main power supply
under-voltage protection) function while the main power shutoff continues
for the setup of Pr6D (Main power-off detection time).


This parameter is invalid when SV.Pr6D (Main power-off detection
time)=1000. Err13 (Main power supply under-voltage protection) is
triggered when setup of SV.Pr6D is long and P-N voltage of the main
converter falls below the specified value before detecting the main power
shutoff, regardless of the SV.Pr65 setup.

Setup value

0

<1>

Action of main power low voltage protection

Turns the servo off according to SV.Pr67 (Error response

at main power-off).

When the main power is shut off during Servo-ON, the

driver will trip due to Err13 (Main power supply under-

voltage protection).

64

0 to 1

<0>

Output signal

selection

Set the function of the positioning completion output/in-deceleration
output pin (COIN/DCLON: CN X5 Pin 27).

Setup value

<0>

1

Description

COIN (Positioning completion output)

DCLON (In-deceleration output)

67

0 to 9

<0>

Error response at

main power-off

When SV.Pr65 (Undervoltage error response at main power-off) is 0, you
can set up,
1) the action during deceleration and after stalling
2) the clearing of deviation counter content
after the main power is shut off.

Setup

value

<0>

1

2

3

4

5

6

7

8

9

During deceleration

DB

Free-run

DB

Free-run

DB

Free-run

DB

Free-run

Emergency stop

Emergency stop

After stalling

DB

DB

Free-run

Free-run

DB

DB

Free-run

Free-run

DB

Free-run

Action

Deviation counter

content

Clear

Clear

Clear

Clear

Hold

Hold

Hold

Hold

Clear

Clear

68

0 to 3

<0>

Error response

action

You can set up the action during deceleration or after stalling when some
error occurs while either one of the protective functions of the driver is
triggered.

(DB: Dynamic Brake action)

The content of the deviation counter will be cleared when clearing the
alarm.

Setup

value

<0>

1

2

3

During deceleration

DB

Free-run

DB

Free-run

After stalling

DB

DB

Free-run

Free-run

Action

Deviation counter

content

Hold

Hold

Hold

Hold

(DB: Dynamic Brake action)

In case of the setup value of 8 or 9, torque limit during deceleration will be
limited by the setup value of SV.Pr6E (Emergency stop torque set up).