beautypg.com

Table, Table heading, Table row – HP A9834-9001B User Manual

Page 70: Cell, Memory, Typical power (watts), Cooling (btu/hr), Breaker power (watts), Table body

background image

Chapter 2

System Specifications

Environmental Requirements

70

b. These numbers are valid only for the specific

configurations shown. Any upgrades may require a
change to the breaker size. A 5-wire source utilizes a
4-pole breaker, and a 4-wire source utilizes a 3-pole
breaker. The protective earth (PE) ground wire is not
switched.

Table 2-16

Typical HP Integrity Superdome/sx2000 for Single-core CPU

Configurations

a

Cell

Memory

IO

Typical

Power

(Watts)

Cooling

(Btu/Hr)

Breaker

Power

(Watts)

b

8

32

4

9130

31181

11503

8

16

2

7260

24794

9147

8

8

4

7783

26580

9806

8

8

2

6823

23302

8596

8

4

4

7260

24794

9147

8

4

2

6300

21516

7938

6

16

4

6968

23797

8779

6

16

2

6008

20518

7570

6

8

4

6640

22677

8366

6

8

2

5680

19398

7156

6

4

4

6325

21601

7969

6

4

2

5365

18322

6759

4

16

4

5813

19852

7324

4

16

2

4853

16574

6114

4

8

4

4647

15870

5855

4

8

2

3687

12592

4645

4

4

4

5382

18380

6781

4

4

2

4422

15102

5571

2

16

2

3656

12486

4606

2

8

2

3534

12069

4453

2

4

2

3423

11690

4313

a. Values in Table 2-15 are based on 25 W load I/O cards, 1

GB DIMMs and four Intel

 Itanium 2 single-core

processors with 9 MB cache per cell board.

This manual is related to the following products: