beautypg.com

Table, Table heading, Table row – HP A9834-9001B User Manual

Page 69: Cell, Memory, Typical power (watts), Cooling (btu/hr), Breaker power (watts), Table body

background image

Chapter 2

System Specifications

Environmental Requirements

69

WARNING

Do not connect a 380 to 415 V ac supply to a 4-wire PDCA. This is a safety hazard and
will result in damage to the product. Line-to-line or phase-to-phase voltage
measured at 380 to 415 V ac must always be connected using a 5-wire PDCA.

Table 2-15

Typical HP Integrity Superdome/sx2000 for Dual-core CPU

Configurations

a

a. Values in Table 2-15 are based on 25 W load I/O cards, 1

GB DIMMs and four Intel

 Itanium 2 dual-core

processors with 18 MB or 24 MB cache per cell board.

Cell

Memory

IO

Typical

Power

(Watts)

Cooling

(Btu/Hr)

Breaker

Power

(Watts)

b

8

32

4

9490

32382

11957

8

16

2

7620

26001

9601

8

8

4

8140

27776

10256

8

8

2

7180

24500

9047

8

4

4

7620

26001

9601

8

4

2

6660

22726

8391

6

16

4

7320

24978

9223

6

16

2

6360

21702

8013

6

8

4

7000

23886

8820

6

8

2

6040

20610

7610

6

4

4

6680

22794

8417

6

4

2

5720

19518

7207

4

16

4

6170

21054

7774

4

16

2

5210

17778

6564

4

8

4

5960

20337

7509

4

8

2

5000

17061

6300

4

4

4

5760

19655

7257

4

4

2

4800

16379

6048

2

16

2

4010

13683

5052

2

8

2

3890

13274

4901

2

4

2

3780

12898

4763

This manual is related to the following products: