Table, Table heading, Table row – HP A9834-9001B User Manual
Page 69: Cell, Memory, Typical power (watts), Cooling (btu/hr), Breaker power (watts), Table body
Chapter 2
System Specifications
Environmental Requirements
69
WARNING
Do not connect a 380 to 415 V ac supply to a 4-wire PDCA. This is a safety hazard and
will result in damage to the product. Line-to-line or phase-to-phase voltage
measured at 380 to 415 V ac must always be connected using a 5-wire PDCA.
Table 2-15
Typical HP Integrity Superdome/sx2000 for Dual-core CPU
Configurations
a
a. Values in Table 2-15 are based on 25 W load I/O cards, 1
GB DIMMs and four Intel
Itanium 2 dual-core
processors with 18 MB or 24 MB cache per cell board.
Cell
Memory
IO
Typical
Power
(Watts)
Cooling
(Btu/Hr)
Breaker
Power
(Watts)
b
8
32
4
9490
32382
11957
8
16
2
7620
26001
9601
8
8
4
8140
27776
10256
8
8
2
7180
24500
9047
8
4
4
7620
26001
9601
8
4
2
6660
22726
8391
6
16
4
7320
24978
9223
6
16
2
6360
21702
8013
6
8
4
7000
23886
8820
6
8
2
6040
20610
7610
6
4
4
6680
22794
8417
6
4
2
5720
19518
7207
4
16
4
6170
21054
7774
4
16
2
5210
17778
6564
4
8
4
5960
20337
7509
4
8
2
5000
17061
6300
4
4
4
5760
19655
7257
4
4
2
4800
16379
6048
2
16
2
4010
13683
5052
2
8
2
3890
13274
4901
2
4
2
3780
12898
4763