beautypg.com

Environmental requirements, This section provides the, Temperature and humidity specifications – HP A9834-9001B User Manual

Page 68: Table, Table heading, Table row, Temperature (dry bulb oc), Relative humidity %; noncondensing, Dew point, Rate of chg (˚c/hr, max)

background image

Chapter 2

System Specifications

Environmental Requirements

68

Environmental Requirements

This section provides the environmental, power dissipation, noise emission, and air flow specifications.

Temperature and Humidity Specifications

NOTE

The values in Table 2-14 meet or exceed all ASHRAE specifications.

Power Dissipation

Table 2-15 lists the power requirements by configuration (number of cell boards, amount of memory per cell,
and number of I/O chassis) for the HP Integrity Superdome/sx2000.

The table contains two columns of power numbers expressed in watts. The Breaker Power column lists the
power used to size the wall breaker at the installation site. The Typical Power column lists typical power.
Typical power numbers can be used to assess the average utility cost of cooling and electrical power.
Table 2-15 also lists the recommended breaker sizes for 4-wire and 5-wire sources.

Table 2-13

Operational Physical Environment Requirements

a

a. The maximum elevation for the operating environment is 3050 meters.

Temperature (dry bulb

ο

C)

b

b. Dry bulb temperature is the regular ambient temperature. Derate maximum dry bulb temperature

1°C/300 m above 900 m.

Relative Humidity %;

Noncondensing

Dew Point

c

c. Must be noncondensing environment.

Rate of Chg
(°C/hr, max)

Allowable

d,e

d. With installed media, the minimum temperature is 10°C and maximum relative humidity is

limited to 80%. Specific media requirements may vary.

e. Allowable: equipment design extremes as measured at the equipment inlet.

Recommended

f

f. Recommended: target facility design and operational range.

Allowable

e

Recommended

f

15 to 32

(59

ο

to 90

ο

F)

20 to 25

(68

ο

to 77

ο

F)

20 to 80

40 to 55

17

5

Table 2-14

Nonoperational Physical Environment Requirements

Storage

Powered Off (Installed)

Temp (°C, dry
bulb - regular
ambient temp.)

Rel Hum %;
Noncondensing

Dew point
(max)

Temp (°C, dry
bulb - regular
ambient temp.)

Rel Hum %;
Noncondensing

Dew point
(max)

-40 to 60

8 to 90

32

5 to 45

8 to 90

29

This manual is related to the following products: