Figure21 pdca locations, System power requirements, Table28 – HP A9834-9001B User Manual
Page 65: Table, Table heading, Table row, Requirement, Value, Comments, Table body
![background image](/manuals/92959/65/background.png)
Chapter 2
System Specifications
Electrical Specifications
65
Figure 2-1
PDCA Locations
System Power Requirements
Table 2-8 and Table 2-9 list the ac power requirements for an HP Integrity Superdome/sx2000 system. These
tables provide information to help determine the amount of ac power needed for your computer room.
Table 2-8
Power Requirements (Without Support Management Station)
Requirement
Value
Comments
Nominal input voltage
200/208/220/230/
240 V ac rms
Input voltage range (minimum to maximum)
200 to 240 V ac
rms
Autoselecting (measured at
input terminals)
Frequency range (minimum to maximum)
50/60 Hz
Number of phases
3
Maximum in-rush current
90 A (peak)
PDCA 0
PDCA 1