Figure329 checking pdca test points (5-wire), Table, Table33 4- and 5-wire voltage ranges – HP A9834-9001B User Manual
Page 107: Table heading, Table row, Wire, Table body, L2 to l3: 200-240 v, L1 to n: 200-240 v, L2 to l1: 200-240 v
Chapter 3
Installing the System
Setting Up the System
107
Figure 3-29
Checking PDCA Test Points (5-Wire)
Table 3-3
4- and 5-Wire Voltage Ranges
4-Wire
5-Wire
L2 to L3: 200-240 V
L1 to N: 200-240 V
L2 to L1: 200-240 V
L2 to N: 200-240 V
L1 to L3: 200-240 V
L3 to N: 200-240 V
N to Ground:
a
a. Neutral to ground voltage can vary from millivolts to
several volts depending on the distance to the
ground/neutral bond at the transformer. Any voltage
over 3 V should be investigated by a site preparation
or power specialist.
Detail A
Detail B
Test points
Retaining screw
(See detail)