Figure329 checking pdca test points (5-wire), Table, Table33 4- and 5-wire voltage ranges – HP A9834-9001B User Manual

Page 107: Table heading, Table row, Wire, Table body, L2 to l3: 200-240 v, L1 to n: 200-240 v, L2 to l1: 200-240 v

background image

Chapter 3

Installing the System

Setting Up the System

107

Figure 3-29

Checking PDCA Test Points (5-Wire)

Table 3-3

4- and 5-Wire Voltage Ranges

4-Wire

5-Wire

L2 to L3: 200-240 V

L1 to N: 200-240 V

L2 to L1: 200-240 V

L2 to N: 200-240 V

L1 to L3: 200-240 V

L3 to N: 200-240 V

N to Ground:

a

a. Neutral to ground voltage can vary from millivolts to

several volts depending on the distance to the
ground/neutral bond at the transformer. Any voltage
over 3 V should be investigated by a site preparation
or power specialist.

Detail A

Detail B

Test points

Retaining screw

(See detail)