Table row, Product label maximum current, 3-phase, 4-wire, 44 a rms – HP A9834-9001B User Manual

Page 66: Per phase at 200 to 240 v ac, Product label maximum current, 3-phase, 5-wire, 24 a rms, Power factor correction, 95 minimum, Ground leakage current (ma), 5 ma

background image

Chapter 2

System Specifications

Electrical Specifications

66

WARNING

Beware of shock hazard. When connecting or removing input power wiring, always
connect the ground wire first and disconnect it last.

Component Power Requirements

Table 2-8 and Table 2-9 list the ac power requirements for an HP Integrity Superdome/sx2000 system. These
tables provide information to help determine the amount of ac power needed for the computer room.

I/O Expansion Cabinet Power Requirements

The I/O expansion cabinet (IOX) requires a single-phase 200-240V ac input. Table 2-10 lists the ac power
requirements for the I/O expansion cabinet.

NOTE

The IOX accommodates two ac inputs for redundancy.

Product label maximum current, 3-phase, 4-wire

44 A rms

Per phase at 200 to 240 V ac

Product label maximum current, 3-phase, 5-wire

24 A rms

Per phase at 200 to 240 V ac

Power factor correction

0.95 minimum

Ground leakage current (mA)

> 3.5 mA

See the following WARNING.

Table 2-9

Component Power Requirements (Without Support Management
Station)

Component

Component Power Required

50 Hz to 60 Hz

a

a. A number to use for planning, to allow for enough power to upgrade through

the life of the system.

Maximum configuration for SD16

8,200 VA

Maximum configuration for SD32

12,196 VA

Cell board

900 VA

I/O card cage

500 VA

Table 2-8

Power Requirements (Without Support Management Station)

Requirement

Value

Comments