2 connect through rs-485 interface – GeoVision GV-R1352 Card Reader (13.56 MHz) User Manual
Page 27

18
2.3.2 Connect through RS-485 Interface
The following diagrams use
GV-RK1352
and
GV-AS810 Controller
as an example. Up to
eight readers can be connected together to the RS-485 interface on GV-AS810 Controller.
⚫
Connecting four or less readers to GV-AS810 Controller:
RS
4
8
5
12V
A+
A-
B+
B-
GND
Reader 1
(Black)
(Light Blue)
(Blue)
(Red)
Reader 4
GV-AS810 Controller
GV-RK1352 or GV-R1352
Wire Color
Function
Black
GND
Light Blue
RS-485 -
Blue
RS-485 +
Red
DC 7.5 ~ 12V
⚫
Connecting five or more readers to GV-AS810 Controller:
For readers five to eight, connect the RS-485 cable to the RS-485 interface on GV-
AS810 Controller and then connect the 12V power output and GND of the reader to a
12V DC power output on the controller.
(Red)
(Black)
RS
4
8
5
12V
A+
A-
B+
B-
GND
(Black)
(Light Blue)
(Blue)
(Red)
GV-AS810 Controller
12
V
O
U
T
P
U
T
12V
GND
12V
GND
12V
GND
Readers 1-4
Readers 5-8
GV-RK1352 or GV-R1352