ProSoft Technology MVI56-PDPMV1 User Manual
Page 57

MVI56-PDPMV1 ♦ ControlLogix Platform
Start Here
PROFIBUS DPV1 Master
User Manual
ProSoft Technology, Inc.
Page 57 of 255
March 22, 2011
3 Fill the module properties as required:
Parameter
Value
Name
Enter a module identification string. Example: MVI56PDPMV1_2
Description
Enter a description for the module. Example: ProSoft communication
module for PROFIBUS communication.
Comm Format
Select DATA-INT
Slot
Enter the slot number in the rack where the MVI56-PDPMV1 module is
located.
Input Assembly
Instance
1
Input Size
Enter the number of words per backplane input block to copy from the
module to the processor. The allowable range is from 12
TO
250 words.
Each input block will reserve 8 words for general purposes (CRC, block/CIP
handshaking). The remainder is reserved for PROFIBUS input data.
Output Assembly
Instance
2
Output Size
Enter the number of words per backplane output block to copy from the
module to the processor. The allowable range is from 5
TO
248 words. Each
output block will reserve 5 words for general purposes (CRC and block
handshaking). The remainder is reserved for PROFIBUS output data.
Configuration
Assembly Instance
4
Configuration Size
0
4 Click OK to confirm. The new module is now visible:
5 Expand the Tasks folder, and then expand the MainTask folder.
6 On the MainProgram folder, click the right mouse button to open a shortcut
menu. On the shortcut menu, choose N
EW
R
OUTINE
.
7 In the New Routine dialog box, enter the name and description of your
routine, and then click OK.