ProSoft Technology MVI56-PDPMV1 User Manual
Page 171

MVI56-PDPMV1 ♦ ControlLogix Platform
Mailbox Messaging
PROFIBUS DPV1 Master
User Manual
ProSoft Technology, Inc.
Page 171 of 255
March 22, 2011
Command and Response Layout: Stop Slave
Command
Response
Message ID
(ID)
(ID)
Message information
4002h
0002h
Command
000Ch
000Ch
Stop Slave
Data size
007Eh
007Eh
Frame count
0001h
0001h
Frame number
0001h
0001h
Offset high
0000h
0000h
Offset low
0000h
0000h
Extended word 1
-
-
Extended word 2
-
-
Extended word 3
-
-
Extended word 4
-
-
Extended word 5
-
-
Extended word 6
-
-
Extended word 7
-
Additional Fault Information
Extended word 8
-
Fault Information
Message data word 1
Slave 0
Slave 1
Slave 0
Slave 1
Message data word 2
Slave 2
Slave 3
Slave 2
Slave 3
Message data word 3 to
62
...
...
...
...
Message data word 63 Slave 124
Slave 125
Slave 124
Slave 125
Command:
Message data word 1-63
Byte-array stating which slave/slaves to stop. Array index is equal to slave
address.
0: Do not affect slave
1: Stop slave
2-255: Reserved