ProSoft Technology MVI56-PDPMV1 User Manual
Page 158

Mailbox Messaging
MVI56-PDPMV1 ♦ ControlLogix Platform
User Manual
PROFIBUS DPV1 Master
Page 158 of 255
ProSoft Technology, Inc.
March 22, 2011
Command and Response Layout: Set Slave Address
Command
Response
Message ID
(ID)
(ID)
Message information
4002h
0002h
Command
0006h
0006h
Set Slave Address
Data size
(Size of data)
(Size of data)
No. of Slave Data bytes (n)
Frame count
0001h
0001h
Frame number
0001h
0001h
Offset high
0000h
0000h
Offset low
0000h
0000h
Extended word 1
Current
Slave Addr.
New Slave
Address
Current
Slave Addr.
New Slave
Address
Extended word 2
Slave Ident Number
Slave Ident Number
Extended word 3
No_add_
Chg
-
No_add_
Chg
Extended word 4
-
-
Extended word 5
-
Error Code 1 Error Code 2
Extended word 6
-
Error Code 3 Error Code 4
Extended word 7
-
Return Code
Extended word 8
Fault Information
Message Data byte 1
Slave Data 1
Slave Data 1
Message Data byte 2
Slave Data 2
Slave Data 2
Message Data byte 3
Slave Data 3
Slave Data 3
...
...
...
Message Data byte "n"
Slave Data n
Slave Data n
Message Information
Refer to Message Information (page 173).
Current Slave Address
Range 1 to 125; specifies the current address of the slave.
New Slave Address
Range 1 to 125; specifies the new address of the slave.