background image

Reference

MVI56-PDPMV1 ♦ ControlLogix Platform

User Manual

PROFIBUS DPV1 Master

Page 200 of 255

ProSoft Technology, Inc.

March 22, 2011

PROFIBUS Master Specifications

Up to 125 slaves can be connected with a repeater
Up to 1536 cyclic bytes input and 1536 bytes output data
Supports Extended Diagnostic Data
RS-485 optically isolated PROFIBUS interface with on board DC-DC

converter

Acyclic communications (DPV1), Read and Write
Alarm handling (DPV1)
Supports Sync and Freeze commands
Supports PROFIdrive 3.1 compliant parameter read and write operations
Supports Multicast and Broadcast telegrams (DPV1)

PROFIBUS Master Port

DB-9F optically isolated RS-485
Ready, Run, Error and Token LED Indicators
PROFIBUS DPV1 RS-485 interface with a 9-pin D shell female connector

and isolated opto-couplers