ProSoft Technology MVI56-PDPMV1 User Manual
Page 242

Reference
MVI56-PDPMV1 ♦ ControlLogix Platform
User Manual
PROFIBUS DPV1 Master
Page 242 of 255
ProSoft Technology, Inc.
March 22, 2011
Byte Offset
Start
End
Name
Description
110
111
Reserved
Reserved for future use
112
113
Module backplane read count
Rollover counter of the number of MVI56-PDPMV1 to processor
backplane read data transfers
114
115
Module backplane write count
Rollover counter of the number of MVI56-PDPMV1 to processor
backplane write data transfers
116
117
Module backplane error count
Rollover counter of the number of MVI56-PDPMV1 to processor
backplane data transfers that have failed
118
119
File Error Word
Bitmapped value that indicates which files are not present
Bit 0: Problem with PDPMV1.CFG file
Bit 1: Not used
Bit 2: Problem with PDPMV1.DDB file
Bit 3: Problem with PDPMV1.XML file
Bits 4 to 15 not used.
If this word has a value other than 0, the CFG ERR LED on the
module will be illuminated.
120
145
Reserved
Reserved for future use
146
147
In mailbox queue count
Number of message in the in mailbox queue
148
149
Out mailbox queue count
Number of message in the out mailbox queue
150
151
Alarm queue count
Number of message in the alarm queue
152
153
Last out mailbox message ID
processed from output image
Last out mailbox message ID processed from output image
154
155
Current in mailbox control index
Current in mailbox control index
156
157
Current alarm control index
Current alarm control index
158
496
Reserved for future use
496
497
Index of Output image to receive (1 to 4 for data, 0 or -1 if no
data)
498
499
Block index of -1 or 0 for status block
Output Data Block (Block ID = 1 to n)
This block contains the PROFIBUS output data to be sent from the processor to
the module.
Output Data Block Format (Output Image)
You can find the contents of the Output Data Block (Output Image) in the
MVI56PDPMV1.Output user controller tags in RSLogix.
Byte Offset
Start
End
Name
Description
0
0
Write Block ID
Block number of this write block 1 to n
1
2
PROFIBUS CRC32 value
Computed for PROFIBUS Config