MVI56-PDPMV1 ♦ ControlLogix Platform
Diagnostics and Troubleshooting
PROFIBUS DPV1 Master
User Manual
ProSoft Technology, Inc.
Page 181 of 255
March 22, 2011
Processor
Status
Module
Status
PROFIBUS Master
Status
PROFIBUS Master
Status LED Description
PROFIBUS
Master is
stopped
RUN
ACTIVE
COM STAT (OFF):
Master is not
communicating with
configured slaves.
DBASE STAT (GREEN):
PROFIBUS has been
configured.
TKN HOLD (GREEN):
Module is holding the
PROFIBUS token.
MSTR STAT (RED):
Master is in STOP mode.
CPU is in
Program
mode
PROG
ACTIVE
COM STAT (OFF):
Master is not
communicating with
configured slaves.
DBASE STAT (GREEN):
PROFIBUS has been
configured.
TKN HOLD (GREEN):
Module is holding the
PROFIBUS token.
MSTR STAT (RED):
Master is in STOP mode.
CPU is in
Program
mode
PROG
ACTIVE
COM STAT (OFF):
Master is operating but
there are no slaves
responding.
DBASE STAT (GREEN):
PROFIBUS has been
configured.
TKN HOLD (GREEN):
Module is holding the
PROFIBUS token.
MSTR STAT (GREEN):
Master is in operating
mode.
As previously indicated in this User Manual, the module requires the correct
sample program loaded to the processor for correct initialization and operation. If
the sample program is not set up correctly, then the module might not fully
initialize or allow access to the debug menu through PCB.
As indicated below, it is required to have a sample program loaded in the
processor in order to allow debug menu access through PCB and to be able to
reconfigure the MVI56-PDPMV1 module.
Also, if you observe the MSTR STAT LED as RED or blinking GREEN/RED it
means that an incorrect sample ladder logic was loaded to the processor (not
matching the actual module mode (LEGACY or FLEX).