ProSoft Technology MVI56-PDPMV1 User Manual
Page 168

Mailbox Messaging
MVI56-PDPMV1 ♦ ControlLogix Platform
User Manual
PROFIBUS DPV1 Master
Page 168 of 255
ProSoft Technology, Inc.
March 22, 2011
Command and Response Layout: Set Operating Mode
Command
Response
Message ID
(ID)
(ID)
Message information
4002h
0002h
Command
0002h
0002h
Set Operation Mode
Data size
0000h
0000h
Frame count
0001h
0001h
Frame number
0001h
0001h
Offset high
0000h
0000h
Offset low
0000h
0000h
Extended word 1
Mode
Conf. Req
Mode
Conf. Req
Extended word 2
-
-
Extended word 3
-
-
Extended word 4
-
-
Extended word 5
-
-
Extended word 6
-
-
Extended word 7
-
-
Extended word 8
-
Fault Information
Mode
40h: STOP
80h: CLEAR
C0h: OPERATE
Conf. Req.
00h: Confirmation is not required
01h: Confirmation required. All confirmations are automatically sent by the
Master; the user is not required to send a confirmation message.
Fault Information
If "Invalid Other" is returned in the Message Information word in the header of the
response, information about the fault can be found here. Refer to Return Codes
(page 174) for more information.
0100h: Invalid operating mode
FF00h: Module not initialized