ProSoft Technology MVI56-PDPMV1 User Manual
Page 241

MVI56-PDPMV1 ♦ ControlLogix Platform
Reference
PROFIBUS DPV1 Master
User Manual
ProSoft Technology, Inc.
Page 241 of 255
March 22, 2011
Byte Offset
Start
End
Name
Description
74
74
PROFIBUS pad byte to make data word aligned (not used)
75
75
PROFIBUS Master Operating
State
PROFIBUS Master operating state
0x0000=Offline
0x4000=Stop
0x8000=Clear
0xC000=Operate
76
77
PROFIBUS Ident Number
PROFIBUS Master PNO Ident number. Bytes will be swapped
78
81
PROFIBUS Master Serial Number Unique 32-bit serial number for the PROFIBUS Master
82
83
PROFIBUS Software Version
Software version number for the PROFIBUS Master software
Example for Version 1.40:
High Byte - 0x40
Low Byte - 0x01
84
85
PROFIBUS Master Module Status Represents the PROFIBUS Master module’s operating status
Bit 2=Application Status
0 - Application Stopped
1 - Application Running
Bit 8=Data exchange (FBRS)
0 - There is no data exchange with any of the assigned slaves
1 - There is data exchange with at least one of the assigned
slaves
Bit 9=Slave input frozen/cleared (FBFC)
0 - A slave's inputs in the IN area are cleared if a slave is not in
Data Exchange
1 - A slave’s inputs in the IN area are frozen if a slave is not in
Data Exchange
Bit 12=Reset (RDR)
0 - No action
1 - A reset is requested by the PROFIBUS Master module
because a new database has been downloaded
86
89
PROFIBUS configuration
Checksum
CRC32 checksum for PROFIBUS Master configuration
downloaded from configuration utility
90
93
MVI56 Module configuration
checksum
MVI56-PDPMV1 for module configuration downloaded from
configuration utility
94
95
Application program scan counter
MVI56-PDPMV1 module program scan counter. Can be used to
gauge application code scan time performance
96
97
Module PROFIBUS output image
data update counter
Counter representing the number of times the output data image
is transferred to the module’s internal Master
98
99
Module PROFIBUS input image
data update counter
Counter representing the number of times the input data image
is transferred from the module’s internal Master
100
101
Module out mailbox counter
Module out mailbox counter
102
103
Module in mailbox counter
Module in mailbox counter
104
105
Module alarm IND receive counter Number of spontaneous alarm messages received from slave
106
107
Module alarm CON receive
counter
Number of confirmation messages received from slaves
indicating that the slave received the confirmation message from
the MVI56-PDPMV1 module
108
109
Reserved