Page 192

Diagnostics and Troubleshooting
MVI56-PDPMV1 ♦ ControlLogix Platform
User Manual
PROFIBUS DPV1 Master
Page 192 of 255
ProSoft Technology, Inc.
March 22, 2011
Viewing Control Registers
Press [3] to view information about the PROFIBUS Master’s Control Registers.
Use this command to view general information about the module, such as the
firmware version and its serial number. The module status contains two possible
codes:
0400 = module is running but not communicating with slaves
0401 = module is running and communicating with slaves
If the module is in STOP mode, the status code is displayed as 0400.
Exiting the Program
Press [ESC]
to restart the module and force all drivers to be loaded. The module
will use the configuration stored in the module's flash memory to configure the
module.
Input Database View Menu
Press [I] from the Main Menu to open the Input Database View menu. Use this
menu command to view the current contents of the module’s database. Press [?]
to view a list of commands available on this menu.
Displaying the Current Page of Registers Again
Press [S]
from the Database View menu to show the current page of registers
again.
This screen displays the current page of 100 registers in the database.