ProSoft Technology MVI56-PDPMV1 User Manual
Page 233

MVI56-PDPMV1 ♦ ControlLogix Platform
Reference
PROFIBUS DPV1 Master
User Manual
ProSoft Technology, Inc.
Page 233 of 255
March 22, 2011
Byte Offset
Start
End
Name
Description
58
73
PROFIBUS Slave
Diagnostic Status
This is a 16-byte array with bit fields where one bit is assigned to
each slave station address. When a slave leaves the "Deactive"
state for the first time, the associated bit is set. This bit is then
cleared when the slave enters "Data Exchange" state. If a slave
indicates "Extended Diagnostics" when it is in "Data Exchange"
state, the associated bit is set. For the bit/slave relationship,
refer to the Slave List Structure below.
Slave List Structure
Byte Offset
Start
End
Name
Description
74
74
PROFIBUS pad byte to make data word aligned (not used)
75
75
PROFIBUS Master
Operating State
PROFIBUS Master operating state
0x0000=Offline
0x4000=Stop
0x8000=Clear
0xC000=Operate
76
77
PROFIBUS Ident
Number
PROFIBUS Master PNO Ident number. Bytes will be swapped
78
81
PROFIBUS Master
Serial Number
Unique 32-bit serial number for the PROFIBUS Master
82
83
PROFIBUS Software
Version
Software version number for the PROFIBUS Master software
Example for Version 1.40:
High Byte - 0x40
Low Byte - 0x01