PROGRAMMING CHARACTERISTICS - ANALOG
Analog remote control
selection Activate with jumper at analog program-
ming connector
Recognized during power up.
isolation Safety Extra Low Voltage (SELV)
referenced to chassis
Programming by voltage
voltage 0-10V
Programmable
current minimal value-10V
Programming by resistance
voltage 0-10K ohms
Programmable
current 0-10K ohms
Readback
0-10V proportional signal
Proportional to analog control volt-
age/resistance
Remote inhibit
TTL compatible
Composite status flag
Isolated form C contacts
Programmable functions (PAR. 2.7.10)
Programming time
20 milliseconds
10% to 90% E
out
PROGRAMMING CHARACTERISTICS - DIGITAL
Digital remote control
isolation Safety Extra Low Voltage (SELV)
referenced to chassis
format compatible with SCPI protocols
W95, W98 and NT operating systems
Programming resolution
0.024% of Emax and Ilim
Programming accuracy
0.05% of Emax and Ilim
Readback resolution
0.024% of Emax and Ilim
Readback accuracy
0.1% of Emax and Ilim
Status reporting
OVP, OCP, OTP, output lead fault
(OLF), fan failure, power loss
See PAR. 1.4.4 and 1.4.9
NOTES:
(1) Requires the a-c input to be recycled for restart
(2) OVP and OCP limit adjustment is disabled in Remote Analog Mode
TABLE 1-2. KLP SPECIFICATIONS (Continued)
SPECIFICATION
RATING/DESCRIPTION
CONDITION