GENERAL (ENVIRONMENTAL) SPECIFICATIONS
Temperature
operating
-20 to +50 deg C
Rated load. Derate at 25W per °C
between 50 and 70°C.
storage
-40 to +85 deg C
Cooling
3 internal d-c fans
exhaust to the rear
Humidity
0 to 95% RH
non condensing
Shock
20g, 11msec +/- 50% half sine
non operating
Vibration
5 -10 Hz
10mm double amplitude
3-axes, non-operating
10-55 Hz
2g
3-axes, non-operating
Altitude
sea level to 10000 ft.
0-3,000 ft: 100%, linear derating to
70% of power at 10,000ft.
PHYSICAL CHARACTERISTICS
Dimensions
English 1.75'H x 19"W x 17.5"D
depth excluding connectors and termi-
nal blocks (See Figure 1-3.)
metric 44.45 x 482.6 x 443.7 mm
Weight
English 15 lbs
metric 6.82kg
Source power connector
IEC 320-C19 appliance inlet
250 Va-c, 16A (VDE);
125V a-c, 20A (UL)
Load connections
8-36V models Nickel plated copper busbars
Provision for safety covers
75-600V models Shocksafe Euroblock
Analog programming port.
15 pin D-sub
Digital programming port
primary Standard GPIB connector
IEEE 488.2 (GPIB)
secondary 9 pin D-sub
RS 232
Direct output control
5 position low profile Euroblocks
PROGRAMMING CHARACTERISTICS - LOCAL
Local control
rotary encoders
panel mounted
Local control resolution
Coarse ~100 LSB/step
depress control for Fine resolution
Fine 1 LSB/step
Setting range
0-100% of rating
KLP will decrement limit to maintain
1200 W maximum
Power up settings
voltage defaults to zero
DIP switch 3 set to off. (If DIP switch 3
set to ON, power up voltage and cur-
rent set to last value set prior to power
down.)
current defaults to minimal value
Protection Limits
(2)
Emax 20-120%
Programmable; accessed via front
panel protect switch or IEE 488.2 bus
command.
Imax 60-120%
NOTES:
(1) Requires the a-c input to be recycled for restart
(2) OVP and OCP limit adjustment is disabled in Remote Analog Mode
TABLE 1-2. KLP SPECIFICATIONS (Continued)