Controller Copy Function (Copy)
The Copy function is used to copy (or clone) all the settings from one
controller to other controllers requiring exactly the same setup and pro-
gramming (i.e. type of input, scaling, decimal point, filter, bypass, etc.).
Warning!
Only the PDA1200 meter copy cable must be used for
meter-to-meter interfacing. The PDA1200 is a special
eight-conductor flat cable with two wires swapped.
Using standard CAT5 or other cable will cause dam-
age to both controllers.
Figure 22: Controller Copy Connection
Copy Function Requirements
To successfully copy settings from one controller to another, both
controllers must have:
1. Same
software
version
2. Same baud rate setting
See Determining Software Version, page 86 for instructions.
PDA1200 Controller Copy Cable