Baud, Slavid, Tr dly – Precision Digital PD6310 User Manual
Page 77: Serial t-byt, Parity

Model PD6210 & PD6310 Batch Controllers
Instruction Manual
77
Modbus RTU Serial Communications (serial)
The controller is equipped with serial communications capability as a 
standard feature using Modbus RTU Serial Communication Protocol. 
To communicate with a computer or other data terminal equipment, an 
RS-232. RS-422/485, or USB adapter option is required; see Ordering 
Information
on page 7 for details.
Warning!
Do not connect any equipment other than Precision 
Digital’s expansion modules, cables, or controllers to 
the RJ45 M-LINK connector. Otherwise damage will 
occur to the equipment and the controller. 
Note: More detailed instructions are provided with each optional serial
communications adapter.
Note: Refer to the P
RO
V
U
®
Modbus Register Tables located at
www.predig.com for details.
 baud
 
Serial
 SlavId
 
Serial
 tr dly
 
Serial
serial
 t-byt
 
Serial
 Parity
 
Serial
When using more than one controller in a multi-drop mode, each control-
ler must be provided with its own unique address. The controller address 
(Slave ID) may be programmed between 1 and 247. The transmit delay 
may be set between 0 and 199 ms. The parity can be set to even, odd, 
or none with 1 or 2 stop bits. 
The PD6210 can also be connected to another PD6210 with a special 
PDA1200 cable, allowing the user to copy all the settings from one con-
troller to another, using the Copy function. 