Precision Digital PD6310 User Manual
Page 46
Model PD6210 & PD6310 Batch Controllers
Instruction Manual
46
Programming the Rate/Totalizer (prog)
It is very important to read the following information, before proceeding
to program the controller:
PD6210:
The PD6210 is factory calibrated prior to shipment to read in mil-
liamps and volts depending on the input selection. The calibration
equipment is certified to NIST standards.
Use
the
Scale
menu to scale process inputs (e.g. 4-20 mA). A cali-
brated signal source is not needed to scale the controller.
PD6310
The PD6310 has been factory calibrated to read input frequency in
Hz (pulses/sec). The calibration equipment is certified to NIST stan-
dards.
Use the K-Factor menu to match the rate/totalizer with a flowmeter’s
k-factor (pulse/unit of measure).
Or use the Scale menu to scale the pulse input (pulse/sec) without a
signal source.
Or use Cal menu to calibrate the rate/totalizer using a signal source.
The Program menu contains the following menus:
1. Scale without a signal source
2. Calibrate with a calibrated signal source
3. Total time base & conversion factor
4. Grand total time base & conversion factor
5. Total reset mode for total & grand total
The process inputs may be calibrated or scaled to any display value
within the range of the controller.
p r o g
s C a l e
P r o g
C a l
P r o g
t C F
P r o g
t t b
P r o g
G ran d
T ot al
S e t t in gs
t r s t
P r o g
Additional parameters, not needed for most applications, are pro-
grammed in the Advanced Features menu; see ADVANCED OPERA-
TION AND PROGRAMMING, page 69.