Model PD6210 & PD6310 Batch Controllers
Instruction Manual
44
Scaling and Calibration
It is very important to read the following information, before proceeding
to program the controller:
There
is
no need to recalibrate
the controller when first received
from the factory.
All inputs are factory calibrated. The calibration equipment used is
certified to NIST standards.
Use
the
Scale
menu to enter the scaling without a signal source.
Use
the
Calibrate
menu to apply a signal from a calibrator or a
flowmeter for the scaling.
Note:
The Scale and Calibrate functions are exclusive of each oth-
er. The controller uses the last function programmed. Only one of
these methods can be employed at a time. The Scale and Calibrate
functions can use up to 32 points (default is 2). The number of
points should be set in the Advanced menu under the Multi-Point Li-
nearization (Linear) menu selection prior to scaling or calibration of
the controller, see page 79 for details.