Model PD6210 & PD6310 Batch Controllers
Instruction Manual
12
INPUT 
IMPEDANCE 
Pulse input: Greater than 300 k
 @ 1 kHz.
Open collector/switch input: 4.7 k
 pull-up to 5 V.
ACCURACY
±0.03% of calibrated span ±1 count
TEMPERATURE 
DRIFT 
Rate display is not affected by changes in temperature.
MULTI-POINT 
LINEARIZATION 
2 to 32 points
LOW-FLOW 
CUTOFF 
0-999999 (0 disables cutoff function)
DECIMAL POINT Up to five decimal places or none:
d.ddddd
, d.dddd, d.ddd, d.dd, d.d,
or
dddddd
CALIBRATION
May be calibrated using K-factor, internal calibration, or by 
applying an external calibration signal. 
K-FACTOR
Field programmable K-factor converts input pulses to rate in 
engineering units. May be programmed from 0.00001 to 
999,999 pulses/unit. 
CALIBRATION 
RANGE 
Input 1 signal may be set anywhere in the range of the 
controller; input 2 signal may be set anywhere above or 
below input 1 setting. 
Minimum input span between any two inputs is 10 Hz. 
An Error message will appear if the input 1 and input 2 
signals are too close together. 
FILTER
Programmable contact de-bounce filter: 40 to 999 Hz max-
imum input frequency allowed with low speed filter. 
TIME BASE
Second, minute, hour, or day
GATE
Low gate: 0.1-99.9 seconds 
High gate: 2.0-999.9 seconds 
Batch Controller Rate/Totalizer Display
RATE DISPLAY 
INDICATION 
-99999 to 999999, lead zero blanking. “R” LED illuminates 
while displaying rate. 
BATCH TOTAL & 
GRAND TOTAL 
DISPLAY 
0 to 999,999; automatic lead zero blanking. “T” LED is illumi-
nated while displaying batch total. “GT” LEDs are illuminated 
while displaying grand total. Up to 999,999 for batch to-
tal/preset. Up to 999,999,999 with grand total-overflow fea-
ture. “
oF
” is displayed to the left of grand total overflow and
▲ LED is illuminated.
BATCH TOTAL 
DECIMAL POINT 
Up to five decimal places or none:
d.ddddd
, d.dddd, d.ddd, d.dd, d.d,
or
dddddd
Total decimal point is independent of rate decimal point.