Model PD6210 & PD6310 Batch Controllers

Instruction Manual

12

INPUT
IMPEDANCE

Pulse input: Greater than 300 k

 @ 1 kHz.

Open collector/switch input: 4.7 k

 pull-up to 5 V.

ACCURACY

±0.03% of calibrated span ±1 count

TEMPERATURE
DRIFT

Rate display is not affected by changes in temperature.

MULTI-POINT
LINEARIZATION

2 to 32 points

LOW-FLOW
CUTOFF

0-999999 (0 disables cutoff function)

DECIMAL POINT Up to five decimal places or none:

d.ddddd

, d.dddd, d.ddd, d.dd, d.d,

or

dddddd

CALIBRATION

May be calibrated using K-factor, internal calibration, or by
applying an external calibration signal.

K-FACTOR

Field programmable K-factor converts input pulses to rate in
engineering units. May be programmed from 0.00001 to
999,999 pulses/unit.

CALIBRATION
RANGE

Input 1 signal may be set anywhere in the range of the
controller; input 2 signal may be set anywhere above or
below input 1 setting.
Minimum input span between any two inputs is 10 Hz.
An Error message will appear if the input 1 and input 2
signals are too close together.

FILTER

Programmable contact de-bounce filter: 40 to 999 Hz max-
imum input frequency allowed with low speed filter.

TIME BASE

Second, minute, hour, or day

GATE

Low gate: 0.1-99.9 seconds
High gate: 2.0-999.9 seconds

Batch Controller Rate/Totalizer Display

RATE DISPLAY
INDICATION

-99999 to 999999, lead zero blanking. “R” LED illuminates
while displaying rate.

BATCH TOTAL &
GRAND TOTAL
DISPLAY

0 to 999,999; automatic lead zero blanking. “T” LED is illumi-
nated while displaying batch total. “GT” LEDs are illuminated
while displaying grand total. Up to 999,999 for batch to-
tal/preset. Up to 999,999,999 with grand total-overflow fea-
ture. “

oF

” is displayed to the left of grand total overflow and

▲ LED is illuminated.

BATCH TOTAL
DECIMAL POINT

Up to five decimal places or none:

d.ddddd

, d.dddd, d.ddd, d.dd, d.d,

or

dddddd

Total decimal point is independent of rate decimal point.