Model PD6210 & PD6310 Batch Controllers
Instruction Manual
74
Function Keys & Digital I/O Available Settings
Display Description
Display
Description
Start
Start batch
Lit gt
GT on little display
stop
Pause/stop batch
Lit bc
Batch count display
srtstp
Start/stop combo
disabl
Disable input/button
Rly d
Disable all relays
menu
Enter menu (DI only)
Rly e
Enable all relays
Right
Right/F1(DI only)
O Hold
Output level hold
up
Up/F2 (DI only)
D Hold
Display hold
enter
Enter/F3 (DI only)
big Hi
Max on big display
AcH
Acknowledge relays
big Lo
Min on big display
Rst t
Reset total
big Hl
Max/min on big
display
Rst Gt
Reset grand total
Lit Hi
Max on little display
Rst bc
Reset batch count
Lit Lo
Min on little display
Rst Hi
Reset max
Lit HL
Max/min little display
Rst Lo
Reset min
F On 1
Force relay 1 on
Rst HL
Reset max & min
F On 2
Force relay 2 on
relay
Relay menu
F On 3
Force relay 3 on
Preset
Change preset
F On 4
Force relay 4 on
Set 2
Set point 2 – 8
Advanced Setup and Calibration
Multi-Point Calibration & Scaling
The controller is set up at the factory for 2-point linear calibration. The
number of points for multi-point calibration/scaling is set up in the Ad-
vanced
Features menu. Up to 32 linearization points may be selected.
See page 79 for details.
MeterView
®
Pro Software
The controller can be programmed and operated using the PC-based
MeterView Pro software available for free download at www.predig.com.
Batches may be started, paused, and stopped, through the monitoring
window of the MeterView Pro software. Preset and preclose values may
be changed, and the total and grand total reset.
Data logging for one controller at the time is available with MeterView
Pro software. More advanced data acquisition may be accomplished by
using any Modbus RTU compliant software.