Pd6210 process input, Pd6310 pulse input – Precision Digital PD6310 User Manual
Page 11
Model PD6210 & PD6310 Batch Controllers
Instruction Manual
11
PD6210 Process Input
INPUTS
Field selectable:
0-20, 4-20 mA,
10 V (0-5, 1-5, 0-10 V), Modbus PV (Slave)
ACCURACY
±0.03% of calibrated span ±1 count,
square root & programmable exponent accuracy range:
10-100% of calibrated span
TEMPERATURE
DRIFT
0.005% of calibrated span/
C max from 0 to 65C ambient,
0.01% of calibrated span/
C max from -40 to 0C ambient
SIGNAL INPUT
CONDITIONING
Linear, square root, or programmable exponent
MULTI-POINT
LINEARIZATION
2 to 32 points
PROGRAMMA-
BLE EXPONENT
1.0001 to 2.9999
LOW-FLOW
CUTOFF
0-999999 (0 disables cutoff function)
DECIMAL POINT Up to five decimal places or none:
d.ddddd
, d.dddd, d.ddd, d.dd, d.d,
or
dddddd
CALIBRATION
RANGE
Input
Range
Minimum Span
Input 1 & Input 2
4-20 mA 0.15 mA
10 V
0.10 V
An Error message will appear if the input 1 and input 2
signals are too close together.
INPUT
IMPEDANCE
Voltage ranges: greater than 1 M
Current ranges: 50 - 100
(depending on resettable fuse impedance)
INPUT
OVERLOAD
Current input protected by resettable fuse, 30 VDC max.
Fuse resets automatically after fault is removed.
PD6310 Pulse Input
INPUTS
Field selectable: Pulse or square wave 0-5 V, 0-12 V, or
0-24 V @ 30 kHz; TTL; open collector 4.7 k
pull-up to 5 V
@ 30 kHz; NPN or PNP transistor, switch contact 4.7 k
pull-up to 5 V @ 40 Hz; Modbus PV (Slave)
LOW VOLTAGE
MAG PICKUP
(Isolated)
Sensitivity: 40 mVp-p to 8Vp-p
MINIMUM INPUT
FREQUENCY
0.001 Hz
Minimum frequency is dependent on high gate setting.
MAXIMUM INPUT
FREQUENCY
30,000 Hz (10,000 for low voltage mag pickup)