Error Message (Error)
An error message indicates that the calibration or scaling process was not
successful.
After the error message is displayed, the controller reverts to input 2 dur-
ing calibration or scaling and to input 1 during internal calibration, allow-
ing the appropriate input signal to be applied or programmed.
The error message might be caused by any of the following conditions:
1. Input signal is not connected to the proper terminals, or it is con-
nected backwards.
2. Wrong signal selection in Setup menu.
3. Minimum input span requirements not maintained.
Minimum Input Span
The minimum input span is the minimum difference between input 1 and 2
signals required to complete the calibration or scaling of the controller.
Input range
Input 1 & input 2 span
4-20 mA
0.15 mA
10 VDC
0.10 VDC