beautypg.com

Precision Digital PD6310 User Manual

Page 83

background image

Model PD6210 & PD6310 Batch Controllers

Instruction Manual

83

Error Message (Error)

An error message indicates that the calibration or scaling process was not
successful.
After the error message is displayed, the controller reverts to input 2 dur-
ing calibration or scaling and to input 1 during internal calibration, allow-
ing the appropriate input signal to be applied or programmed.

The error message might be caused by any of the following conditions:
1. Input signal is not connected to the proper terminals, or it is con-

nected backwards.

2. Wrong signal selection in Setup menu.
3. Minimum input span requirements not maintained.

Minimum Input Span

The minimum input span is the minimum difference between input 1 and 2
signals required to complete the calibration or scaling of the controller.

Input range

Input 1 & input 2 span

4-20 mA

0.15 mA

10 VDC

0.10 VDC

This manual is related to the following products: