Display Parameter
Action/Setting
Description
Act 1
Action 1
Set relay 1 action
1
Auto
Automatic
Set relay for automatic reset
A-man
Auto-manual
1
Set relay for automatic & manual reset
any time
1
LatCH
Latching
1
Set relay for latching operation (relays
assigned to rate)
1
Lt-CLr
Latching-
cleared
1
Set relay for latching operation with ma-
nual reset only after alarm condition has
cleared (relays assigned to rate)
1
Altern
Alternate
2
Set relay for pump alternation control
(relays assigned to rate)
2
Sampl
Sampling
Set relay for sampling operation (rate or
GT)
OFF
Off
Disable relay and front panel status LED
(Select Off to enable Interlock feature)
Set 1
Set 1
Program set point 1
RSt 1
Reset 1
Program reset point 1
RLY 2
Relay 2
Relays 2-8 setup
Note: Relays 5-8 are shown, only if ex-
pansion relay module is installed.
FaiLSF
Fail-safe
Enter
Fail-safe menu
FLS 1
Fail-safe 1
Set relay 1 fail-safe operation
on
On
Enable fail-safe operation
off
Fail-safe off
Disable fail-safe operation
DeLAY
Delay
Enter relay
Time Delay menu
DLY 1
Delay 1
Enter relay 1 time delay setup
On 1
On
Set relay 1 On time delay
OFF 1
Off
Set relay 1 Off time delay
break
Loop break
Set relay condition if loop break detected
(For mA input only)
iGnorE
Ignore
Ignore loop break condition
(Processed as a low signal condition)
On
On
Relay goes to alarm condition when loop
break is detected