Isolated 4-20 ma transmitter output – Precision Digital PD6310 User Manual
Page 14

Model PD6210 & PD6310 Batch Controllers
Instruction Manual
14
RELAY 
OPERATION 
Batch control 
Automatic (non-latching)
1
Sampling 
Off (disable unused relays and enable Interlock feature) 
Manual on/off control mode 
Secondary Functions
2
 Pump alternation control (2 to 8 relays) 
 Latching (requires manual acknowledge) 
RELAY RESET
User selectable via front panel buttons, digital inputs, or PC
1. Automatic reset only (non-latching), when the input
passes the reset point or total is reset to zero.
2. Automatic + manual reset at any time (non-latching) 
3. Manual reset only, at any time (latching) 
4. Manual reset only after alarm condition has cleared (L) 
Note: Digital inputs may be assigned to acknowledge relays 
programmed for manual reset. It is not recommended to 
change the functions of front panel buttons to manual reset.
ALARM TIME 
DELAY 
0 to 999.9 seconds, on & off relay time delays 
Programmable and independent for each relay. 
FAIL-SAFE 
OPERATION 
Programmable and independent for each relay. 
Note: Relay coil is energized in non-alarm condition. 
In case of power failure, relay will go to alarm state.
ALARM AUTO 
INITIALIZATION 
When power is applied to the controller, relays will reflect 
the state of the input to the controller.
1
1. Alarms are active only when the batch is running. 
2. These functions are not functional when the unit is being used as a batch 
controller with total set to yes.
Isolated 4-20 mA Transmitter Output
OUTPUT 
SOURCE 
Rate/process, total, grand total, max, min, set points 1-8, 
Modbus register, or manual control mode 
SCALING RANGE 1.000 to 23.000 mA for any display range.
CALIBRATION
Factory calibrated: 4.000 to 20.000 = 4-20 mA output
ANALOG OUT 
PROGRAMMING 
23.000 mA maximum for all parameters: 
Overrange, underrange, max, min, and break 
ACCURACY
± 0.1% FS ± 0.004 mA
TEMPERATURE 
DRIFT 
0.4 µA/
C max from 0 to 65C ambient,
0.8 µA/
C max from -40 to 0C ambient
Note: Analog output drift is separate from input drift.
ISOLATED 
TRANSMITTER 
POWER SUPPLY 
Terminals I+ & R: 24 VDC
 5% @ 40 mA maximum; may
be used to power the 4-20 mA output or other devices. 
Refer to Figure 6 on page 22 and Figure 17 on page 28. 