beautypg.com

Inp 1, Inp 2, Dis 1 – Precision Digital PD6310 User Manual

Page 49: Dis 2

background image

Model PD6210 & PD6310 Batch Controllers

Instruction Manual

49

Calibrating the Controller with External Source (Cal)

To scale the controller without a signal source refer to Scaling the

Controller (SCALE) page 47.

The controller can be calibrated to display the process variable in engi-
neering units by applying the appropriate input signal and following the
calibration procedure.
The use of a calibrated signal source is strongly recommended to cali-
brate the controller.

CAL

Prog

Inp 1

CAL

Inp 1

I n p 1

Inp 2

CAL

Inp 2

I n p 2

dis 1

Inp 1

00

0

.000

d i s 1

dis 2

Inp 2

1

00.000

d i s 2

The display

flashes while

sensing the

inputs

Warm up the controller for at least 15 minutes before performing

calibration to ensure specified accuracy.

This manual is related to the following products: