5.2 Alarms, Faults, and Errors

YASKAWA ELECTRIC TOEP C710656 08B YASKAWA Power Regenerative Unit - R1000 Instruction Manual

87

Tr

ou

blesh

oot

ing

5

5.2 Alarms, Faults, and Errors

Types of Alarms, Faults, and Errors

Check the digital operator for information about possible faults if the regenerative unit fails to operate.

If problems occur that are not covered in this manual, contact the nearest Yaskawa representative with the following
information:

• Regenerative unit model
• Software version
• Date of purchase
• Description of the problem

Table 5.1

contains descriptions of the various types of alarms, faults, and errors that may occur while operating the

regenerative unit.

If the regenerative unit fails, contact your Yaskawa representative or the nearest Yaskawa sales office.

Table 5.1 Types of Alarms, Faults, and Errors

Type

Response

Faults

When the regenerative unit detects a fault:

• The digital operator displays text indicating the specific fault and the ALM indicator LED remains lit until the

fault is reset.

• The fault interrupts regenerative unit output.
• Some faults allow the user to select the stopping method when the fault occurs.
• Fault output terminals MA-MC will close, and MB-MC will open.
• The regenerative unit will remain inoperable until the fault is cleared. Refer to

Fault Reset Methods on

page 112

.

Minor Faults and Alarms

When the regenerative unit detects an alarm or a minor fault:

• The digital operator displays text indicating the specific alarm or minor fault, and the ALM indicator LED

flashes.

• A multi-function contact output set to be tripped by a minor fault (H2-†† = 10) closes. If the output is set to

be tripped by an alarm, the contact will not close.
Remove the cause of the problem to reset a minor fault or alarm.

Operation Errors

An operation error occurs when parameter settings conflict or do not match hardware settings (such as with an
option card). When the regenerative unit detects an operation error:

• The digital operator displays text indicating the specific error.
• Multi-function contact outputs do not operate.

The regenerative unit will not operate until the error has been reset. Correct the settings that caused the
operation error to clear the error.

Copy Function Errors

Copy Function Errors occur when using the digital operator or the USB Copy Unit to copy, read, or verify
parameter settings.

• The digital operator displays text indicating the specific error.
• Multi-function contact outputs do not operate.

Pressing any key on the digital operator will clear the fault. Investigate the cause of the problem (such as
model incompatibility) and try again.