6.4 Cooling Fans
126
YASKAWA ELECTRIC TOEP C710656 08B YASKAWA Power Regenerative Unit - R1000 Instruction Manual
Installing the Cooling Fan
Reverse the procedure described above to reinstall the cooling fan.
1.
Properly connect the fan power lines.
2.
Place the power supply connectors and cable back into the recess of the regenerative unit.
Figure 6.9
Figure 6.9 Cooling Fan Power Supply Connectors: 2A0035, 4A0035, 4A0043
3.
Install the replacement fan into the regenerative unit.
Figure 6.10
Figure 6.10 Install the Cooling Fan: 2A0035, 4A0035, 4A0043
4.
Tilt up the back end of the fan finger guard and slide the fan finger guard into the opening near the front of the
regenerative unit, then guide the fan finger guard into place.
Figure 6.11
Figure 6.11 Reattach the Fan Cover: 2A0035, 4A0035, 4A0043
A – Back
B – Front
A
B
Insert the fan at an angle so that it tilts
towards the front of the regenerative
unit. Next press down on the back of
the fan that still protrudes from the
regenerative unit so that the fan snaps
into place.
Insertion area
Front of
regenerative unit
Back of
regenerative unit
Fan finger guard
Back of regenerative unit
Front of unit
Hook
Hook
Cross-Section